          There is no author summary for this article yet. Authors can add summaries to their articles on ScienceOpen to make them more accessible to a non-specialist audience.

          Abstract

          Background

          Lowering water heater temperature set points and using less drinking water are common approaches to conserving water and energy; yet, there are discrepancies in past literature regarding the effects of water heater temperature and water use patterns on the occurrence of opportunistic pathogens, in particular Legionella pneumophila. Our objective was to conduct a controlled, replicated pilot-scale investigation to address this knowledge gap using continuously recirculating water heaters to examine five water heater set points (39–58 °C) under three water use conditions. We hypothesized that L. pneumophila levels at the tap depend on the collective influence of water heater temperature, flow frequency, and the resident plumbing ecology.

          Results

          We confirmed temperature setting to be a critical factor in suppressing L. pneumophila growth both in continuously recirculating hot water lines and at distal taps. For example, at 51 °C, planktonic L. pneumophila in recirculating lines was reduced by a factor of 28.7 compared to 39 °C and was prevented from re-colonizing biofilm. However, L. pneumophila still persisted up to 58 °C, with evidence that it was growing under the conditions of this study. Further, exposure to 51 °C water in a low-use tap appeared to optimally select for L. pneumophila (e.g., 125 times greater numbers than in high-use taps). We subsequently explored relationships among L. pneumophila and other ecologically relevant microbes, noting that elevated temperature did not have a general disinfecting effect in terms of total bacterial numbers. We documented the relationship between L. pneumophila and Legionella spp., and noted several instances of correlations with Vermamoeba vermiformis, and generally found that there is a dynamic relationship with this amoeba host over the range of temperatures and water use frequencies examined.

          Conclusions

          Our study provides a new window of understanding into the microbial ecology of potable hot water systems and helps to resolve past discrepancies in the literature regarding the influence of water temperature and stagnation on L. pneumophila, which is the cause of a growing number of outbreaks. This work is especially timely, given society’s movement towards “green” buildings and the need to reconcile innovations in building design with public health.

          Electronic supplementary material

          The online version of this article (doi:10.1186/s40168-015-0134-1) contains supplementary material, which is available to authorized users.

          Related collections

          Most cited references57

          • Record: found
          • Abstract: found
          • Article: not found

          Opportunistic pathogens enriched in showerhead biofilms.

          The environments we humans encounter daily are sources of exposure to diverse microbial communities, some of potential concern to human health. In this study, we used culture-independent technology to investigate the microbial composition of biofilms inside showerheads as ecological assemblages in the human indoor environment. Showers are an important interface for human interaction with microbes through inhalation of aerosols, and showerhead waters have been implicated in disease. Although opportunistic pathogens commonly are cultured from shower facilities, there is little knowledge of either their prevalence or the nature of other microorganisms that may be delivered during shower usage. To determine the composition of showerhead biofilms and waters, we analyzed rRNA gene sequences from 45 showerhead sites around the United States. We find that variable and complex, but specific, microbial assemblages occur inside showerheads. Particularly striking was the finding that sequences representative of non-tuberculous mycobacteria (NTM) and other opportunistic human pathogens are enriched to high levels in many showerhead biofilms, >100-fold above background water contents. We conclude that showerheads may present a significant potential exposure to aerosolized microbes, including documented opportunistic pathogens. The health risk associated with showerhead microbiota needs investigation in persons with compromised immune or pulmonary systems.
            Bookmark
            • Record: found
            • Abstract: found
            • Article: not found

            The role of biofilms and protozoa in Legionella pathogenesis: implications for drinking water.

            Current models to study Legionella pathogenesis include the use of primary macrophages and monocyte cell lines, various free-living protozoan species and murine models of pneumonia. However, there are very few studies of Legionella spp. pathogenesis aimed at associating the role of biofilm colonization and parasitization of biofilm microbiota and release of virulent bacterial cell/vacuoles in drinking water distribution systems. Moreover, the implications of these environmental niches for drinking water exposure to pathogenic legionellae are poorly understood. This review summarizes the known mechanisms of Legionella spp. proliferation within Acanthamoeba and mammalian cells and advocates the use of the amoeba model to study Legionella pathogenicity because of their close association with Legionella spp. in the aquatic environment. The putative role of biofilms and amoebae in the proliferation, development and dissemination of potentially pathogenic Legionella spp. is also discussed. Elucidating the mechanisms of Legionella pathogenicity development in our drinking water systems will aid in elimination strategies and procedural designs for drinking water systems and in controlling exposure to Legionella spp. and similar pathogens.
              Bookmark
              • Record: found
              • Abstract: found
              • Article: not found

              Microbial ecology of drinking water distribution systems.

              The supply of clean drinking water is a major, and relatively recent, public health milestone. Control of microbial growth in drinking water distribution systems, often achieved through the addition of disinfectants, is essential to limiting waterborne illness, particularly in immunocompromised subpopulations. Recent inquiries into the microbial ecology of distribution systems have found that pathogen resistance to chlorination is affected by microbial community diversity and interspecies relationships. Research indicates that multispecies biofilms are generally more resistant to disinfection than single-species biofilms. Other recent findings are the increased survival of the bacterial pathogen Legionella pneumophila when present inside its protozoan host Hartmannella vermiformis and the depletion of chloramine disinfectant residuals by nitrifying bacteria, leading to increased overall microbial growth. Interactions such as these are unaccounted for in current disinfection models. An understanding of the microbial ecology of distribution systems is necessary to design innovative and effective control strategies that will ensure safe and high-quality drinking water.
                Bookmark

                Author and article information

                Contributors
                (417) 437-2550 , wrhoads@vt.edu
                Journal
                Microbiome
                Microbiome
                Microbiome
                BioMed Central (London )
                2049-2618
                1 December 2015
                1 December 2015
                2015
                : 3
                : 67
                Affiliations
                Charles E. Via Department of Civil and Environmental Engineering, Virginia Tech, Blacksburg, VA 24061 USA
                Article
                134
                10.1186/s40168-015-0134-1
                4666224
                26627188
                a33130ea-f84e-4441-ac33-505184859e7a
                © Rhoads et al. 2015

                Open AccessThis article is distributed under the terms of the Creative Commons Attribution 4.0 International License ( http://creativecommons.org/licenses/by/4.0/), which permits unrestricted use, distribution, and reproduction in any medium, provided you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons license, and indicate if changes were made. The Creative Commons Public Domain Dedication waiver ( http://creativecommons.org/publicdomain/zero/1.0/) applies to the data made available in this article, unless otherwise stated.

                History
                : 14 September 2015
                : 17 November 2015
                Categories
                Research
                Custom metadata
                © The Author(s) 2015

                legionella pneumophila,hot water,stagnation,water use,temperature

                Comments

                Comment on this article