      In-situ measurements of wall moisture in a historic building in response to the installation of an impermeable floor

      research-article
      1 , * , , 1 , 2
      UCL Open Environment
      UCL Press
      masonry, wall moisture, historic building, conservation, renovation, capillary rise, evaporation, timber dowel, soil moisture deficit
      Bookmark

            Abstract

            When impermeable ground bearing slabs are installed in old buildings without a damp-proof course, it is a common belief of conservation practitioners that ground moisture will be ‘driven’ up adjacent walls by capillary action. However, there is limited evidence to test this hypothesis.

            An experiment was used to determine if the installation of a vapour-proof barrier above a flagstone floor in a historic building would increase moisture content levels in an adjacent stone rubble wall. This was achieved by undertaking measurements of wall, soil and atmospheric moisture content over a 3-year period. Measurements taken using timber dowels showed that the moisture content within the wall did not vary in response to wall evaporation rates and did not increase following the installation of a vapour-proof barrier above the floor. This indicates that the moisture levels in the rubble wall were not influenced by changes in the vapour-permeability of the floor.

            Main article text

            Introduction

            Water movement through the masonry walls of historic buildings is an important process influencing thermal performance, wall deterioration (e.g., salt weathering), decay of built-in timbers, and damage to the internal finishes and environment (e.g., mould) [1]. Therefore, understanding moisture regimes within historic structures is critical to heritage conservation and the appropriate selection of materials for repair or renovation [2].

            Relatively impermeable concrete ground-bearing slabs are sometimes installed in historic buildings during renovation, but it is unclear if this adversely alters the moisture dynamics of the building. It is believed by many conservation practitioners that if an impermeable ground bearing slab is installed in a historic building during renovation, and particularly those which do not contain a damp-proof course, ground moisture will be ‘driven’ up adjacent walls through capillary action. Although there are references to this phenomenon in the technical literature [3,4], there is limited evidence based on long-term monitoring.

            Water transport in buildings and building materials is site-specific and complex, but is generally dominated by capillary forces and unsaturated flow within the pores of building materials [2,5,6]. It can be difficult to model unsaturated flow through historic masonry walls because it is not always possible to intrusively characterise the physical properties of the wall materials, their heterogeneity and the interfaces between the different materials forming the wall. However, it is possible to measure and model the primary processes influencing the supply and removal of water within walls, to consider the behaviour of the wall as a system. Hall and Hoff [7] developed a quantitative representation of the primary processes controlling moisture migration and wall damp rise in a masonry wall (Fig. 1). This shows that ground moisture (u) is absorbed at the base of a homogenous, porous wall of thickness b. To ensure the conservation of mass, a state of dynamic equilibrium is established if the height of the wetted part of the wall (h) varies in response to the evaporation rate on the wall surface (e).

            Figure 1

            A conceptual model of wall damp rise by Hall and Hoff [7], with soil moisture uptake (u) and wall evaporation (e) driving the saturated wall height (h), in a wall thickness (b).

            The Hall and Hoff [7] conceptual model describes the primary process of moisture migration through porous building materials. However, the wall moisture dynamics in a historic building is further complicated by in situ conditions that are difficult to quantify, measure and model. This includes but is not limited to (i) the heterogeneous nature of old masonry walls, and (ii) the moisture storage and conductivity properties of the materials forming the wall. Therefore, in situ monitoring was identified as the most effective method to measure the response of a masonry wall to the installation of an impermeable floor barrier in a historic building.

            Aim and objectives

            The aim was to determine if moisture levels in the external wall of a historic building were responsive to seasonal potential evaporation rates and if these were influenced by the installation of an impermeable ground bearing slab. The first objective was to determine whether seasonal changes in soil moisture content and evaporative drying influenced moisture levels within the wall. The second objective was to simulate the installation of an impermeable ground bearing slab by sealing the floor with a vapour-proof barrier and measuring changes in wall moisture levels due to the intervention.

            Method

            The monitoring programme

            A 3-year monitoring programme was undertaken to measure moisture levels in a 600 mm thick, composite rubble-core masonry wall at Court House; a private residential property in Caldicot, Wales (Fig. 2). Court House is a Grade II listed building originating from the 16th or 17th Century [8]. The masonry wall was located on the north elevation of the house and formed the external wall of an unheated, flagstone-floored room that was used as a pantry during the monitoring period (Fig. 3).

            Figure 2

            Court House is located in Caldicot, Wales. © Crown copyright and database rights 2021 Ordnance Survey (100025252) using Digimap Ordnance Survey Collection, https://digimap.edina.ac.uk/.

            Figure 3

            The external face of the pantry wall at Court House.

            The monitoring programme included measurements of soil moisture levels at the base of the wall, the evaporative drying on the wall faces and the moisture levels within the wall (Fig. 4), in accordance with the conceptual model (Fig. 1). Details of the electronic sensors are shown in Table 1.

            Figure 4

            Instrumentation installed in a 600 mm thick, rubble-core masonry wall at Courth House to measure wall moisture (%), soil moisture (%) and evaporative drying on the wall face.

            Table 1.

            A summary of electronic sensors installed at Court House

            Type of instrumentMeasurementLocationSource/references
            WS-GP1 weather stationSolar radiation (kWm‒2), air temperature (°C), humidity (%), rainfall (mm/tip), wind speed (ms‒1), wind direction (°)Court House (external)Delta-T Devices, Ltd, Cambridge, UK
            Tinytag Plus 2Internal air temperature (°C) and relative humidity (%)Internal wall at Court HouseGemini Data Loggers, Chichester, UK
            Protimeter Mini, with deep wall probeWall moisture ‘wood moisture equivalent’ (via resistance)(%)Holes drilled into internal wall face at Court House (0.2 m–1.4 m above ground level)Amphenol Advanced Sensors, Taunton, UK
            PR2 Profile ProbeSoil moisture (m3m−3)Court House (0 m–1 m below ground level)Delta-T Devices, Ltd, Cambridge, UK

            The internal structure of the wall was unknown, but walls elsewhere in the property were formed from an inner and outer leaf of stone rubble bedded in lime mortar, with a mortar and rubble-filled core. The wall was rough cast cement rendered and painted on the external face (Fig. 3). It was plastered with a lime-based material and painted on the internal face. A shallow excavation at the property showed that the ground consisted of clay soil mixed with made ground and infilled ground [9], overlain by organic topsoil. A geological map showed that Court House is located on an outcrop of sandstone from the Mercia Mudstone Group [10] but this was not observed in the ground excavation.

            The instrument installation and monitoring began in January 2017. Site visits to measure soil and wall moisture levels were undertaken at approximately monthly intervals between January 2017 and March 2020. A vapour-proof, 0.15 mm thick polyethylene sheet was laid over the floor along the length of the pantry wall and sealed at the edges with tape on 18th September 2019, to simulate the installation of an impermeable ground bearing slab. Supporting laboratory experiments showed that the polyethylene sheet was less permeable than a concrete slab. It therefore simulated a worst-case scenario in terms of creating an impermeable floor. A Tinytag logger was installed beneath the polyethylene sheet to measure the time required to reach a constant humidity (%) reading.

            Instrumentation and measurement

            Figure 4 shows the layout of instrumentation installed at Court House. Evaporative conditions on the internal and external wall faces were continually measured and logged. Externally, a WS-GP1 weather station [11] was installed to measure hourly changes in solar radiation (kWm‒2), air temperature (°C), humidity (%), rainfall (mm/tip), wind speed (ms‒1) and wind direction (°). A Tinytag Plus 2 datalogger [12] was installed at the top of the internal wall face to measure hourly changes in air temperature (°C) and relative humidity (%) directly adjacent to the wall surface.

            Soil moisture was measured using a PR2 Soil Moisture Probe [13,14], inserted into a 1 m long access tube at approximately monthly intervals. The probe has electronic sensors fixed to a 25 mm diameter polycarbonate rod at fixed intervals of 0.1 m, 0.2 m, 0.3 m, 0.4 m, 0.6 m and 1 m below ground level. The sensing elements measure the permittivity (ε) of the soil in a 100 mm radius surrounding the probe. These were logged and converted to volumetric moisture content (θ, %) using a linear relationship for mineral soils:

            (1) θ=ε1.68.4

            Changes in wall moisture were measured indirectly at approximately monthly intervals using (i) timber dowels and (ii) a commercial moisture meter. Seven, 130 mm long, 12 mm diameter holes were drilled into the internal face of the pantry wall in a vertical array at 0.2 m spacing between 0.2 m and 1.4 m above ground level (Fig. 4). Pine dowels (10 mm diameter) were installed into these holes and sealed with plumber’s putty. Weight measurements of the dowels were then taken on site at approximately monthly intervals, to determine changes in their gravimetric moisture content (%). Calibration of the timber dowels showed that they took approximately 14 days to reach equilibrium and provided a good indicator of relative changes in wall moisture, however, absolute values at dowel moisture contents > 15% may be underestimated.

            At approximately monthly intervals, ‘deep wall probes’ were inserted into the wall to measure wall moisture using a Protimeter Mini Moisture Meter [15]. The deep wall probes were inserted into seven pairs of 75 mm deep, 6 mm diameter holes that were drilled 40 mm horizontally apart, directly adjacent to the larger diameter holes which contained the timber dowels, again between 0.2 m and 1.4 m above ground level. These holes were also sealed with plumber’s putty. The Protimeter Mini moisture meter provides a ‘wood moisture equivalent’ reading (6–90%) based on the electrical resistance measured between the probes. The calibration for the Protimeter Mini Moisture Meter was not readily available from the manufacturer, so the meter readings were treated as an approximate measure of relative changes in wall moisture.

            Interpretation of potential evaporative drying

            An approximation for the potential evaporative conditions on the external and internal wall faces were calculated from the weather station and Tinytag measurements of air temperature (°C) and relative humidity (%). The potential evaporation was assumed to be equal to the potential evapotranspiration (PET) calculated using the simple equation by Schendel [16] and appraised for climate modelling by Bormann [17]:

            (2) PET=16·TRH

            where PET is the potential evapotranspiration (mm/day), T is the mean daily temperature (°C) and RH is the mean daily relative humidity (%).

            Interpretation of soil moisture

            The soil moisture levels at the property were calculated from (i) the weather station data and (ii) direct measurements of the soil moisture content profile. Using both approaches it was possible to calculate a soil moisture deficit (SMD) for the soil profile between 0 m and 1 m below ground level.

            The SMD is the volume of water per unit area (mm3mm‒2) that the soil can absorb before reaching field capacity, where the moisture content is in equilibrium and free to drain under gravity [18]. The daily SMD can be calculated from a soil water balance of daily rainfall infiltration and potential evapotranspiration; bounded by SMD equal to zero when the soil is at field capacity and water cannot infiltrate the soil surface. The daily SMD at Court House was calculated using the rainfall, temperature and relative humidity measurements from the weather station, with the PET calculated using Equation 2.

            The measured SMD (SMDm ) was derived from the PR2 Profile Probe measurements of volumetric moisture content (θ) using the approach described by Smethurst et al. [19]. The total SMDm of the soil profile (0–1 m below ground level) was calculated using

            (3) SMDm=inhi(θFCθi)

            where θi is the measured volumetric moisture content in each soil layer (n), of thickness hi . A volumetric moisture content of 38% was assumed at field capacity (θFC ), based on the wettest soil profiles measured.

            Interpretation of wall moisture

            Timber dowels have been used to successfully measure in situ moisture changes in solid brick walls [20] and historic stone walls [21]. Timber dowels absorb moisture over 2 or 3 weeks until they achieve equilibrium with the surrounding wall [22]. Prior to installation, the timber dowels were oven dried at 105 °C for at least 24 h to determine the dry mass (md ). The timber dowels were then weighed at monthly intervals to measure the wet mass (mw ) and enable calculation of the relative changes in gravimetric moisture content (wm ) using:

            (4) wm(%)=(mwmd)md×100%

            It was possible to calculate the wall moisture changes using the potential evaporative drying measurements, for comparison with the timber dowels measurements. Hall and Hoff [7] derived a conceptual model for rising damp moisture movement within a porous masonry wall without finishes (Fig. 1). From this they developed a one-dimensional model of capillary rise dynamics based on sharp front theory. The model shows that water will rise within the pores of a wall via capillary action, if the wall has interconnected pore space and water is available at the base of the wall. Hall and Hoff [7] showed that the steady-state height of water rise (hss ) within a porous wall can be calculated using:

            (5) hss=Sb2eθw1/2

            where S is the sorptivity of the masonry (mm.min‒1/2), e is the evaporation rate (mm.min‒1), θw is the moisture content of the wetted part of the wall (mm3.mm‒3) and b is the wall thickness (mm). Equation 5 was used to calculate the daily, steady-state height of water rise using the daily average PET (mm.min‒1) measured at Court House on both the internal and external wall faces. The wall thickness (b) was 600 mm. The sorptivity (S) and moisture content of the wetted part of the wall (θw ) were not measured but were assumed to be 1.0 mm.min‒1/2 and 0.2, respectively, as used by Hall and Hoff [7].

            Results

            Evaporative drying

            The internal and external temperature (°C) and relative humidity (%) data showed potential evaporative drying during the summer months, followed by reduced drying through the winter months. These seasonal changes are typical of the temperate UK climate [23,24]. Figure 5 shows increased temperature and reduced relative humidity in the summer months (April to September), relative to the cooler, more humid winter months (October to March). A comparison of annual cumulative potential evapotranspiration (PET, mm) and rainfall (mm) shows that PET was greatest in the summer months and least in the winter months, with consistent total, annual cumulative PET (Fig. 6). The calculated cumulative potential evapotranspiration was higher than comparative measurements in southern England [25,26], due to the simple PET model used (Equation 2). Figure 6 shows that 2018 was both wetter (January to June) and drier (July to December) than in 2017 and 2019. According to the conceptual model of wall damp rise (Fig. 1) and Equation 5, these evaporative conditions would lead to greater annual variation in the wall damp rise (mm) in 2018 than in the preceding or succeeding years (2017 and 2019).

            Figure 5

            Daily average temperature (°C) and relative humidity (%) measured internally (Tinytag logger data) and externally (weather station data) at Court House between 2017 and 2020. Note that internal Tinytag data are missing from September 2018 to March 2019 due to instrument damage.

            Figure 6

            Cumulative annual evapotranspiration (ET0, mm) and rainfall (mm) measured by the weather station at Court House. Note that the measurements start on 18/01/2017.

            Soil moisture

            Figure 7 shows soil moisture content profiles measured at the end of winter and the end of summer between 2017 and 2019. The greatest variation in soil moisture content occurred in the near surface, up to 0.4 m below ground level, as is typical in clay soils with grass vegetation at equivalent latitude [18]. Figure 7 shows that the soil moisture content was often below field capacity (θFC = 38%) and that a supply of water was not consistently available at the base of the masonry wall. Figure 8 shows that soil moisture was available at the base of the masonry wall during the winter months (i.e., SMD = 0), while there was a soil moisture deficit (i.e., SMD > 0) during the summer months. This shows that the availability of soil moisture varied seasonally and was not constant, as was assumed in the conceptual model (Fig. 1).

            Figure 7

            Soil moisture content profiles measured at the end of winter (April/May) and the end of summer (July/September) at Court House.

            Figure 8

            SMD (mm) at Court House (i) calculated using daily weather station data and (ii) measured using a PR2 soil moisture probe (up to 1 m below ground level).

            Wall moisture

            Figure 9 shows the dowel moisture (mass) content values taken at approximately monthly intervals between March 2017 and March 2020. The measurements show that the dowel was close to 50% moisture content at the base of the wall and consistently greater than higher up the wall. The data show that the moisture level of the dowels, and by implication the wall, did not vary in response to seasonal evaporation rates. Nor did the dowel moisture levels immediately increase in response to the sealing of the flagstone floor. Measurements with a Tinytag logger (not shown in Fig. 4) showed that moisture levels rapidly increased beneath the vapour-proof barrier within 2 days of installation in September 2019, showing ground moisture transfer through the floor and into the internal environment of the room.

            Figure 9

            Measurements of timber dowel moisture content (by mass) between 0.2 m and 1.4 m above ground level over a 3-year period between 2017 and 2020, including an intervention to seal the floor on 18/09/2019.

            Figure 10 shows the wall moisture levels measured using the moisture meter with a deep wall probe. The wall moisture probe showed consistently lower meter readings at the base of the wall relative to the upper part of the wall. The meter readings were erratic and did not show a temporal trend. It is possible that the meter readings were responding to changes in the internal air temperature and humidity or were influenced by the distribution of salts within the wall [27]. They were not considered to be reliable measurements of wall moisture levels for this study.

            Figure 10

            Protimeter Mini Moisture Meter readings measured between 0.2 m and 1.4 m above ground level over a 3-year period between 2017 and 2020, including an intervention to seal the floor on 18/09/2019.

            Figure 11 shows the height of wall capillary rise calculated using the Hall and Hoff [7] sharp front model, assuming (i) the supply of water at the base of the wall (ii) potential evaporative drying measured on the internal and external wall faces at Court House and (iii) a porous masonry wall with interconnected pores and without finishes. This shows that prior to the installation of the vapour-proof barrier, given the model assumptions, the capillary rise should have varied between 800 mm (summer) and 1200 mm (winter) above ground level. However, the historic masonry wall was not subject to capillary rise, despite the supply of water at the wall base (Fig. 8) and seasonally variable evaporative drying on the wall face (Fig. 6). Inspection of the wall showed that the wall was formed from porous materials, but with large voids and discontinuities that would inhibit capillary flow. Therefore, the fabric of the wall itself did not facilitate water being ‘driven up’ by capillary action. This was confirmed by the measurements showing that the wall moisture levels did not vary seasonally, nor did they vary in response to the installation of a vapour-proof barrier to seal the floor (Fig. 9).

            Figure 11

            The height of wall capillary rise calculated using the Hall and Hoff [7] sharp front model using PET derived from temperature and relative humidity data measured (i) on the internal wall face and (ii) on the external wall face. Note: Internal wall face data are missing for September 2018 to March 2019. Extreme capillary rise values for the external wall face have been omitted for clarity.

            Pre-existing moisture damage was observed on the internal plaster surface of the lower part of the wall (approx. 200 mm above ground level) prior to instrumentation, but the moisture levels did not vary at this location during the monitoring period. It is possible that localised capillary rise occurred within the plaster and caused the damage. However, this did not affect the core of the wall, nor was the base of the wall influenced by the installation of the vapour-proof barrier during the monitoring period.

            Conclusions

            Instrumentation was installed in a historic building to measure changes in wall moisture content and to measure the response of the wall to vapour-sealing of the ground floor. The monitoring programme was based on a conceptual model of capillary rise within the pores of the wall, driven by evaporative drying on the wall surface.

            The following conclusions can be drawn from the results presented:

            1. The rubble-fill, masonry wall at Court House was not susceptible to wall moisture fluctuations due to capillary rise, driven by evaporative drying. The moisture levels in the wall did not vary in response to changes in potential evaporative drying on the internal and external faces of the wall, despite the availability of soil moisture at the base of the wall during the winter months.

            2. Measurements of soil moisture content showed that the supply of water from the soil is seasonally variable. Water is often not available for capillary rise within the pores of a wall during the drier summer months, when soil moisture levels are below field capacity. The supply of water for capillary uptake within a wall is greatest during the winter months, when the ground is more likely to be close to, or at field capacity. This seasonal variation is comparable to measurements in other clay soils in the south of England [18,19].

            3. If an impermeable ground bearing slab was installed in this building, ground moisture would not necessarily be ‘driven’ up adjacent walls. Measurements beneath the vapour-proof barrier confirmed that moisture was moving through the flagstone floor, but this did not increase the wall moisture. Sealing of the flagstone floor using a vapour-proof barrier did not increase the moisture levels within the rubble-fill, masonry wall at Court House.

            4. The in-situ measurements of wall moisture at Court House contradicted predictions based on a theoretical model of capillary rise for an idealised wall. This is because the heterogeneous fabric of the rubble-fill wall (from visual inspection) seemed to contain a discontinuous pore network between the materials forming the wall. This restricted capillary flow between the wall elements and capillary rise within the wall.

            Funding

            This research was funded by Historic England.

            Acknowledgements

            The authors would like to thank Alison Henry (Historic England), Kate Leighton (Static Dynamic) and Brian Ridout (Ridout Associates) for helpful discussions. Thanks are also due to former University of Bath staff, David Muddle, David Surgenor and David Williams for help with experimental measurements. Supplementary weather data for the Figures presented in this paper are openly available from the University of Bath Research Data Archive [28] at https://doi.org/10.15125/BATH-01101.

            Open data and materials availability statement

            The datasets generated during and/or analysed during the current study are available in the repository: https://doi.org/10.15125/BATH-01101

            Declarations and conflicts of interest

            Research ethics statement

            The authors declare that research ethics approval for this article was provided by an internal ethics review at the University of Bath.

            Consent for publication statement

            The author declares that research participants’ informed consent to publication of findings – including photos, videos and any personal or identifiable information – was secured prior to publication.

            Conflicts of interest statement

            The author declares no conflict of interest with this work.

            References

            1. El-Turki A, Ball RJ, Holmes S, Allen WJ, Allen GC. Environmental cycling and laboratory testing to evaluate the significance of moisture control for lime mortars. Constr Build Mater. 2010. Vol. 24(8):1392–7. [Cross Ref]

            2. Franzoni E. Rising damp removal from historical masonries: a still open challenge. Constr Build Mater. 2014. Vol. 54:123–36. [Cross Ref]

            3. Trotman P, Sanders C, Harrison H. Understanding Dampness. Vol. Vol. 640. Berkshire, UK: BRE Bookshop. 2004

            4. Historic England. Energy efficiency and historic buildings: insulating solid ground floors. 2016. https://historicengland.org.uk/advice/technical-advice/energy-efficiency-and-historic-buildings/

            5. Hall C, Hamilton A, Hoff WD, Viles HA, Eklund JA. Moisture dynamics in walls: response to micro-environment and climate change. Proc R Soc A: Math Phys Eng Sci. 2011. Vol. 467(2125):194–211. [Cross Ref]

            6. Hall C, Hoff WD. Water Transport in Brick, Stone and Concrete. CRC Press. London, UK: 2021

            7. Hall C, Hoff WD. Rising damp: capillary rise dynamics in walls. Proc R Soc A: Math Phys Eng Sci. 2007. Vol. 463(2084):1871–84. [Cross Ref]

            8. DataMapWales. Cof Cymru, Listed buildings asset on DataMapWales. 2021 Accessed 2021 https://cadw.gov.wales/advice-support/cof-cymru/search-cadw-records

            9. Ford J, Kessler H, Cooper AH, Price SJ, Humpage AJ. An Enhanced Classification of Artificial Ground. Ground British Geological Survey Open Report. 2010. p. 32

            10. British Geological Survey. Geological Survey of England and Wales 1:63,360/1:50,000 geological map series, New Series. Sheet 250, Chepstow. 1981

            11. Delta-T. WS-GP1 Weather station, quick start guide. https://delta-t.co.uk/wp-content/uploads/2016/10/WS-GP1-Weather-Station-QSG.pdf

            12. Gemini. Tinytag Plus 2 Data Sheet. 2021 Accessed 2021 https://www.geminidataloggers.com/data-loggers/tinytag-plus-2/tgp-4017

            13. Delta-T. User manual for the SDI-12 Profile Probe. Version 4.1. 2016. https://delta-t.co.uk/wp-content/uploads/2016/09/PR2_SDI-12-_User_Manual_version_4_1.pdf

            14. Qi Z, Helmers MJ. The conversion of permittivity as measured by a PR2 capacitance probe into soil moisture values for Des Moines lobe soils in Iowa. Soil Use Manag. 2010. Vol. 26(1):82–92. [Cross Ref]

            15. Amphenol. Protimeter moisture meters. 2021 Accessed 2021 www.protimeter.com

            16. Schendel U. Vegetationswasserverbrauch und -wasserbedarf. Kiel: Habilitation. 1967. p. 137

            17. Bormann H. Sensitivity analysis of 18 different potential evapotranspiration models to observed climatic change at German climate stations. Clim Change. 2011. Vol. 104(3):729–53. [Cross Ref]

            18. Smethurst JA, Clarke D, Powrie W. Seasonal changes in pore water pressure in a grass-covered cut slope in London Clay. Geotechnique. 2006. Vol. 56(8):523–37. [Cross Ref]

            19. Smethurst JA, Briggs KM, Powrie W, Ridley A, Butcher DJE. Mechanical and hydrological impacts of tree removal on a clay fill railway embankment. Géotechnique. 2015. Vol. 65(11):869–82. [Cross Ref]

            20. Walker R, Pavía S, Dalton M. Measurement of moisture content in solid brick walls using timber dowel. Mater Struct. 2016. Vol. 49(7):2549–61. [Cross Ref]

            21. Larsen PK. Moisture measurement in tirsted church. J Archit Conserv. 2004. Vol. 10(1):22–35. [Cross Ref]

            22. Ridout B. Timber Decay in Buildings: The Conservation Approach to Treatment. London: E & F Spon. 2000

            23. Jenkins GJ, Perry MC, Prior MJ. The Climate of the UK and Recent Trends. UK Climate Projections. 2009

            24. Hollis D, McCarthy M, Kendon M, Legg T, Simpson I. HadUK-Grid – a new UK dataset of gridded climate observations. Geosci Data J. 2019. Vol. 6(2):151–9. [Cross Ref]

            25. Smethurst JA, Clarke D, Powrie W. Factors controlling the seasonal variation in soil water content and pore water pressures within a lightly vegetated clay slope. Géotechnique. 2012. Vol. 62(5):429–46. [Cross Ref]

            26. Briggs KM, Smethurst JA, Powrie W, O’Brien AS. Wet winter pore pressures in railway embankments. Proc Inst Civ Eng Geotech Eng. 2013. Vol. 166(5):451–65. [Cross Ref]

            27. Franzoni E, Bandini S. Spontaneous electrical effects in masonry affected by capillary water rise: the role of salts. Constr Build Mater. 2012. Vol. 35:642–6. [Cross Ref]

            28. Briggs KM, Ball RJ, McCaig I. Dataset for Daily Weather Data (2017–2020) Measured in Caldicot, Wales. Bath: University of Bath Research Data Archive. 2022. [Cross Ref]

            Author and article information

            Journal
            UCL Open Environ
            UCLOE
            UCL Open Environment
            UCL Open Environ
            UCL Press (UK )
            2632-0886
            08 November 2022
            2022
            : 4
            : e046
            Affiliations
            [1 ]Department of Architecture and Civil Engineering, University of Bath, Bath, BA2 7AY, UK
            [2 ]Historic England, Swindon, UK
            Author notes
            *Corresponding author: E-mail: K.M.Briggs@ 123456bath.ac.uk
            Author information
            https://orcid.org/0000-0003-1738-9692
            https://orcid.org/0000-0002-7413-3944
            Article
            10.14324/111.444/ucloe.000046
            10171423
            53659428-92f8-4e63-a515-42392af066ec
            © 2022 The Authors.

            This is an open access article distributed under the terms of the Creative Commons Attribution Licence (CC BY) 4.0, which permits unrestricted use, distribution and reproduction in any medium, provided the original author and source are credited.

            History
            : 16 December 2021
            : 20 August 2022
            Page count
            Figures: 11, Tables: 1, References: 28, Pages: 11
            Categories
            Research Article

            masonry,conservation,renovation,capillary rise,evaporation,timber dowel,soil moisture deficit,historic building,wall moisture

            Comments

            Comment on this article